0,26 € netto
The ZM24V24A-600B is a switching power supply designed to work with batteries in uninterruptible DC voltage systems. The device has an output voltage of 24 V and an output power of 600 W. It is intended for industrial electronics and automation, energy, telecommunications and telemetry, surveillance and monitoring systems.
The power supply has an internal relay that disconnects the battery to protect against overdischarge. It also has an additional output for connecting an external battery and an input for connecting a temperature probe.
The most important features:
- 24 V output voltage;
- 24V output power
- output current 24 A;
- four-state battery charging current switch;
- accelerated charging function with temperature compensation of voltage;
- possibility of floating operation with temperature compensation of the charging voltage;
- optical signaling: operation from MAINS network (green diode), OCP overcurrent (yellow diode), charging of the cooperating CHRG battery (yellow diode), battery operation BAT - yellow light color 1 / 1s (on / off time), battery failure states BAT (no battery - yellow light before connecting the battery / low battery voltage - yellow light 0.5 / 0.5s).
Specification:
ZM24V24A-600B | |
Input | |
---|---|
Frequency | 47 - 53 Hz |
Power factor | 0,98 |
Voltage |
230 V AC (184 - 253 V AC) 220 V DC (165 - 297 V DC) |
Output | |
Voltage | 24 V |
Current | 24 A |
Power | 600 W |
Characteristic | UPI |
Stabilization of the output voltage | 0,5% |
Buffering voltage per cell at 25 ° C | 2,25 V (2,2 - 2,4 V) |
Quick charge voltage at 25 ° C | 2,36 V / cell |
Temperature compensation factor | -4 mV / °C / cell |
General | |
Efficiency | up to 87% |
External dimensions | 66x111x262 mm |
Weight | 1,7 kg |
Cooling | Active, internal fan |
Power Correction System (PFC) | Yes |
Permissible operating temperature | From -25 to 55 °C |
Protection level |
IP20 PN-EN 60529:2003 |
Standards | |
Functionality | PN-EN 61204:2001+A1:2002 |
Electrical safety |
PN-EN 60950-1:2007+A1:2011 kl. I PN-EN 61204-7:2009 |
Radioelectric disturbances | PN-EN 55022:2006+A1:2011 B class |
EMC immunity |
PN-EN 61204-3:2006 PN-EN 61000-4-2,3,4,5,6,11 |
EMC emission |
PN-EN 61000-3-2::2007 +A1:2010 +A2:2010 PN-EN 61000-3-3:2011 |