-
1,10 zł netto
Delta PMU-27V155WCCA is a buffer power supply with an output voltage of 27V (24 - 28V DC) and a power of about 151 W. The device is distinguished by high work efficiency and reliability. In the event of a mains power failure, the PSU automatically switches to accumulator (battery) power. The product has numerous protections: against overdischarge, against reverse battery connection, against overvoltage, against overload or against overheat. The power supply allows you to select the battery charging current, the range is: 0.5 - 1.5 A.
Othe offered product has two LEDs indicating the power supply (DC OK - green color) and reverse battery connection (red color), it also allows you to connect LEDs indicating AC power and low battery charge. The power supply meets numerous safety standards and is distinguished by a fast AC to DC switching time. The device is covered by a 5-year warranty.
The most important features:
- output voltage - approx 27 V (24 - 28 V);
- output power - 151 W;
- regulation of battery charging current - 0,5 - 1,5 A;
- overdischarge protection;
- the power supply meets numerous safety standards;
- 5-year warranty.
Specification
PMU 27V155WCCA | |
Input parameters | |
---|---|
Nominal input voltage |
100 - 120 V AC 200 - 240 V AC |
Input voltage range |
90 - 132 V AC 180 - 264 V AC |
Nominal input frequency | 50 - 60 Hz |
Input frequency range | 47 - 63 Hz |
Input current |
< 2,5 A at 115 V AC < 1,5 A at 230 V AC |
Efficiency at 100% load |
> 88% przy 115 V AC > 89% przy 230 V AC |
Loss of energy |
Without load < 0,6 W at 115 V AC < 0,7 W at 230 V AC 100% load: < 19 W |
Current shock | < 25 A |
Leakage current | < 0,5 mA przy 264 V AC |
Output parameters | |
Nominal output voltage |
V1: 27,6 V DC B+: 27,1 V DC |
Output voltage tolerance | 2% |
Adjusting the output voltage | 24 - 28 V DC (onlyV1) |
Output current |
Normal mode: V1: 4 A (0 - 5,5 A) B+: 1,5 A (0,5 - 1,5 A) Buffer mode: B+: 5,5 A |
Output power | Max. 151 W |
Stabilization electrical grid changes |
< 0,5% (90 - 132 V AC at 90% load 180 - 264 V AC at 100% load) |
Stabilization from load changes |
< 1% (90 - 132 V AC at 90% load 180 - 264 V AC at 100% load) |
PARD (20 MHz) |
< 150 mVpp przy temp. od -20 do 0 °C < 100 mVpp przy temp. od 0 do 70 °C |
Fixing time |
< 50 ms (100 V AC at 90% load 200 V AC at 100% load) |
Rise time |
< 1000 ms (115 V AC at 90% load 230 V AC at 100% load) |
Holding time |
> 20 ms (115 V AC at 90% load 230 V AC at 100% load) |
Voltage drop between V1 and B + |
Normal mode: 0.5V average Buffer operation: 0.2 V average |
Battery parameters | |
Battery voltage |
SLA battery (lead acid) 2 x 12 V batteries (connected in series) or 1 battery 24 V |
Voltage range |
Continuous operation: 22 - 27.6 V DC Maximum voltage: 32V DC Minimum voltage: 16.5V DC |
Recommended battery capacity | 3.3, 7, 12 or 15 Ah |
Charging time |
From 2 to 10 hours at 1.5 A (depending on battery capacity) |
Charging | CC-CV mode |
Others | |
Dimensions | 178x97x38 mm |
Weight | 0,6 kg |
LED diode |
Green: DC OK Red: reverse battery connection |
Terminals | M 3.5 x 7 |
Signal | JST: XHP-4 |
Wire | AWG 16-14 |
Volume (meter from the power supply) | < 30 dBA |
Backup time depends of battery capacity used:
Output Current |
Time | |||
3,3 Ah | 7 Ah | 12 Ah | 15 Ah | |
---|---|---|---|---|
0,55 A | 330 min | 700 min. | 1208 min. | 1510 min. |
1,1 A | 165 min. | 350 min. | 604 min. | 755 min. |
2,2 A | 82 min. | 175 min. | 302 min. | 377 min. |
3,3 A | 55 min. | 117 min. | 201 min. | 251 min. |
4,5 A | 40 min. | 85 min. | 147 min. | 184 min. |
5,5 A | 33 min. | 70 min. | 120 min. | 151 min. |